Conductors to a single motor ... size = 22A x 1.25 = 27.50A A quick check of Table 310.15(B)(16) reveals that a 10 AWG conductor is rated 35A at 75°C. The branch circuit short circuit and ground fault ...
Motor FLC = 22A [Table 430.250] Conductor’s Size = 22A x 1.25 = 27.5A As per Table 310.15(B)(16), a 10 AWG conductor is rated for 30A at 75°C. Note: The branch circuit short circuit and ground fault ...